Service procedures, 3) meanings of alarm messages – Sanyo KH2442 / CH2442 User Manual

Page 162

Advertising
background image

4. Service procedures

1

2

3

4

Section

SM830082

IV - 6

(3)

Meanings of alarm messages

When using group control, main indoor unit address setting is duplicated.

(For single heat pump type.)

Error in Auto. address setting.

(No. or capacity of judged indoor unit is small.)

Error in Auto. address setting.

(No. or capacity of judged indoor unit is large.)

Indoor unit is detecting error signal from another indoor unit.

• Indoor unit is detecting error signal from the remote controller.
(No serial communications signal)

Remote controller is detecting
error signal from indoor unit.

Indoor unit is detecting error
signal from outdoor unit.

Outdoor unit is detecting error
signal from indoor unit.

Indoor unit is not working
correctly.

Outdoor unit is transmitting error
signal.

Improper setting of indoor unit or
remote controller.

• Serial

commu-
nication
errors

• Mis-setting

Possible Cause of Malfunction

Alarm
message

E1

E2

E3

E4

E5

E6

E7

E8

E9

E12

E14

E15

E16

E18

Protective device in indoor unit
is activated.

Protective device in outdoor
unit is activated.

Protective device in indoor unit
is activated.

Activation of
protective
device

NOTE

RCU

: Remote Control Unit (remote controller)

R.C.

: Refrigerant Circuit

comp. : Compressor

temp. : Temperature

PCB

: Printed Circuit Board

P1

P2

P3

P4

P5

P17

P9

P10

• Thermal protector in indoor fan motor is activated.

• Thermal protector in outdoor fan motor is activated.
• Comp. thermal protector is activated.

Incorrect discharge gas temp. of comp.

High-pressure switch is activated.

Incorrect power supply voltage . Negative phase, defective
phase or voltage drop.

Incorrect discharge gas temp. of comp.

Improper wiring connections of ceiling panel.

Float switch is activated.