background image

4. Service procedures

1

2

3

4

Section

SM830082

IV - 34

7

Solenoid coil of the electronic refrigerant

*Measure the coil resistance.

control valve (ERCV) ………… Indoor unit

Measure the resistance between No. 5 (GRY lead wire) and other terminals (another color of
lead wires) of 5P (WHT) plug connected to the solenoid coil.

Refer to “1-2-(A) Major component specifications”.

8

Compressor motor (CM) ……… Outdoor unit

*Measure the coil resistance.

In case of single -phase compressor

Remove the cover of compressor terminal and measure the resistance

between terminals.

Refer to “1-2 Major component specifications”.

9

Compressor motor magnetic contactor (52C) ………… Outdoor unit

Measure the resistance between A (ORG lead wire) and B (GRY lead wire) terminals on
the compressor motor magnetic contactor.

Refer to “1-3 Other component specifications”.

Check the continuity between contactors.

0

Solenoid coil of 4-way valve (20S) … Outdoor unit

Measure the resistance between No.1 (BLK lead wire) and No.2 (BLK lead wire) terminals
of 2P (BLK) socket connected to the solenoid coil.

Refer “1-3 Other component specifications”.

MODEL

Push button on
the magnetic
contactor

no press

press

FMCA–1UL

Pair of terminals

R – U

S – V

T – W

31 – 32

––––

––––

––––

YES

YES

YES

YES

––––

*Measure the coil resistance.