Sanyo KH2442 / CH2442 User Manual

Page 114

Advertising
background image

I - 110

SM830082

1

2

3

4

5

1. Specifications

Cooling:

Rating Conditions

: Indoor Air Temperature

80

°

F DB / 67

°

F WB

Outdoor Air Temperature

95

°

F DB

Full Load Conditions : Indoor Air Temperature

80

°

F DB / 67

°

F WB

Outdoor Air Temperature 115

°

F DB

Heating:

Rating Conditions

: Indoor Air Temperature

70

°

F DB / 60

°

F WB

Outdoor Air Temperature

47

°

F DB / 43

°

F WB

Full Load Conditions : Indoor Air Temperature

80

°

F DB / —

°

F WB

Outdoor Air Temperature

45

°

F DB / 35

°

F WB

Indoor model: TH2442 / Outdoor model: CH2442

Cooling

Heating

Indoor Unit

Outdoor Unit

Complete Unit

Fan Motor

Fan Motor

Compressor

Performance at

230 - 208 V / 1 phase / 60 Hz

230 - 208 V / 1 phase / 60 Hz

Rating conditions

A

0.4 - 0.4

0.9 - 0.9

10.4 - 11.6

11.7 - 12.9

kW

0.08 - 0.07

0.18 - 0.17

2.29 - 2.26

2.55 - 2.50

Full load conditions

A

0.4 - 0.4

0.9 - 0.9

11.4 - 11.8

12.7 - 13.1

kW

0.08 - 0.07

0.18 - 0.17

2.55 - 2.44

2.81 - 2.68

Starting amperes

A

1 - 1

1 - 1

66 - 60

68 - 62

Indoor Unit

Outdoor Unit

Complete Unit

Fan Motor

Fan Motor

Compressor

Performance at

230 - 208 V / 1 phase / 60 Hz

230 - 208 V / 1 phase / 60 Hz

Rating conditions

A

0.4 - 0.4

0.9 - 0.9

9.4 - 10.0

10.7 - 11.3

kW

0.08 - 0.07

0.18 - 0.17

2.09 - 2.04

2.35 - 2.28

Full load conditions

A

0.4 - 0.4

0.9 - 0.9

11.0 - 11.7

12.3 - 13.0

kW

0.08 - 0.07

0.18 - 0.17

2.45 - 2.42

2.71 - 2.66

Starting amperes

A

1 - 1

1 - 1

66 - 60

68 - 62