2. Processes and functions

Fig. 1

Chart Summary and Explanations

Once the compressor starts, it keeps running for 5 minutes.

Once the compressor stops, it will not start running again for 3 minutes.

If you change the operation mode (HEAT, COOL, or FAN) during the cooling cycle, the
control circuit stops the compressor for 3 minutes.

For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor.

Thermo ON: When room temperature rises 2°F (4°F when set on body sensor) above

the set temperature T˚, (T˚+2°F or T˚+4°F when set on body sensor):

Compressor

ON

Thermo OFF: When the room temperature is –2°F below the set temperature T˚:

Compressor

OFF

2-1

Room Temperature Control

The Unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF.
This process is controlled by the thermostat located in the remote control unit.
The figures on this and the next pages show how each part of the system performs when the
room temperature changes and the thermostat activates the compressor to start (thermo ON)
or stop (thermo OFF). Fig. 1 shows about the cooling cycle, and Fig. 2 shows about the
heating cycle.

(A) Cooling

(THERMO. OFF)

(THERMO. ON)

ROOM TEMP.

THERMO. ON

5 MINUTES

MORE THAN
5 MINUTES 3 MINUTES

SET TEMP

COMPRESSOR

OUTDOOR FAN

(H OR M)

INDOOR FAN

OFF

OFF

OFF

OFF

1

1. Refer to 2-4 Outdoor Fan Speed Control

MORE THAN
3 MINUTES

MORE THAN
5 MINUTES

ON

ON

ON

ON

ON

ON

SET SPEED

T+2

°

F

T–2

°

F

. T

°

F

BODY SENSOR

1133_THS_I

THERMO. OFF

Advertising