Specifications, 2 major component specifications (a) indoor unit – Sanyo KH2442 / CH2442 User Manual

Page 21

Advertising
background image

I - 17

SM830082

1

2

3

4

5

1. Specifications

MODEL No.

TH4242

Source

230 - 208 V / 1 phase / 60 Hz

Remote controller (Option)

RCS - SH80UA, WL

Controller P. C. B Ass'y

CR - TH2442

Control circuit fuse

250 V, 3 A

Fan (Number … diameter)

in.

(mm)

Centrifugal (4 ... 5-29/32(150))

Fan motor

Model

KFG4X - 101C6P

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole … r.p.m. (230 V, High)

rpm

4 ... 1,099

Nominal output

W

100

Coil resistance

BRW - WHT

:

61.05

,

ORG - YEL

:

13.23

(Ambient temperature 68

°

F)

WHT - VLT

:

9.955 ,

YEL

- BLK

:

19.25

VLT

- ORG

:

9.576 ,

BLK

- PNK

:

10.81

Safety device

Operating temperature

Open

°

F

266

±

14.4

Close

°

F

174.2

±

27

Run capacitor

VAC,

µ

F

440 V , 5

µ

F

Electronic expansion valve

Coil

EKV - MOZS584E0

Coil resistance

ORG - GRY

:

46

,

YEL

- GRY

:

46

(Ambient temperature 68

°

F)

RED - GRY

:

46

,

BLK

- GRY

:

46

Valve body

HKV - 30D27

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows … Fins per inch

3 … 14.9

Face area

ft.

2

(m

2

)

3.51 (0.326)

Auto louver motor

Model No.

MT8 - 3C

Auto louver motor … Rated

V, W, rpm

240 VAC , 3 W , 3 rpm

Coil resistance (Ambient temperature 77

°

F)

16,430

±

8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

1-2 Major Component Specifications

(A) Indoor Unit

Advertising