[Connections and Settings in Internal Velocity Control Mode]

Connections and

Settings in Internal

V

e

locity Control Mode

Cautions

(1) After startup, immediately following a first Servo-ON or when you increase Pr22 (Machine stiffness at real time

auto tuning), you may have abnormal noise or oscillation before you identify load inertia or an adaptive filter is

stabilized. However, this doesn’t constitute abnormality if it disappears in no time. If oscillation or noise persists

over 3 reciprocating operations, you should take any of the following measures in any possible order:

1) Write into EEPROM parameters used during normal operation.

2) Decrease Pr22 (Machine stiffness at real time auto tuning).

3) Once set Pr21 (Real time auto tuning set-up) to 0 and disable an adaptive filter. Then, enable real time auto

tuning again (To disable inertia estimation/resetting of adaptive operation, or real time auto tuning, refer to

“Releasing Automatic Tuning Function” on Page 135).

4) Manually set a notch filter (Refer to “To Reduce Mechanical Resonance” on Page 140).

(2) In some cases, after abnormal noise or oscillation is generated, Pr20 (Inertia ratio) or Pr2F (Adaptive filter

frequency) may change to an extreme value. Even in such a case, you should take the measures described

above.

(3) Among results of real time auto gain tuning, Pr20 (Inertia ratio) and Pr2F (Adaptive filter frequency) are written

into EEPROM every 30 minutes. When you power ON again, auto tuning will be carried out using the data as an

initial value.

PrNo.

11

12

13

14

19

1A

1B

1C

20

Name

1st velocity loop gain

1st velocity loop integration time constant

1st speed detection filter

1st torque filter time constant

2nd velocity loop gain

2nd velocity loop integration time constant

2nd speed detection filter

2nd torque filter time constant

Inertia ratio

PrNo.

30

1

Name

Setting

2nd gain action set-up

Parameters to be Set Automatically

The following parameters are tuned automatically. The following parameters are also set up to the following fixed values automatically.

<Remarks>

When real time auto tuning is enabled, you are not allowed to change any parameter to be automatically tuned.