Troubleshooting

Protective
Functions

Overload
Protection
(OL)

*Regenerative
resistor
overload
protection
(REG)

*Encoder
communication
error
protection

Alarm

code No.

16

18

21

Cause

When an integration value of a torque command
exceeds the set overload level, overload protection
is activated based on time limiting characteristics.

(1) Operation lasted long with more load and

effective torque than rating.

(2) Oscillation or hunting operation due to poorly

adjusted gain. Vibration of the motor, and
abnormal sound.

(3) Incorrectly wired motor wires (U, V, W) and

disconnection.

(4) The machine collides, or suddenly gets heavy.

The machine is entangled.

(5) The electromagnetic brake keeps on running.

(6) When more than one driver is used, motor wire

is incorrectly connected to other axis.

Regenerative energy exceeds the capacity of the
regenerative resistor.

(1) The converter voltage increases due to energy

regenerated during deceleration resulting from
high load inertia. In addition, it further rises,
as the regenerative resistor cannot absorb
energy enough.

(2) Because of high rotation speed of the motor,

the regenerative resistor cannot absorb
regeneration within specified deceleration
time.

(3) The operating limit of the external resistor is

limited to 10% duty.

Due to communication breakdown between the
encoder and driver, the encoder cable
disconnection detecting function is activated.
<Caution>
If the above condition occurs before power-on, be
careful as the motor aut omatic recognition
abnormality protection (alarm code No.95) will be
activated when you power on again.

Action

On the waveform graphic screen of PANATERM

®

,

check if torque (current) waveform widely
oscillates up and down. Check load factor and
overload warning display.
(1) Increase the capacity of the motor and driver.

Extend acceleration/deceleration time.
Reduce load.

(2) Readjust gains.

(3) Connect motor wires as per the wiring

diagram. Replace cables.

(4) Free the machine of any tangle. Reduce the

load.

(5) Measure voltage of the brake terminal.

Release the brake.

(6) Correctly connect motor and encoder wiring to

eliminate a mismatch between the wires and axes.

Check the load factor of the regenerative resistor
in monitor mode. You must not use the driver for
the purpose of continuous damping of
regeneration.
(1) Check an operating pattern (waveform

graphic). Check the load factor of the
regenerative resistor and display of over-
regeneration warning. Increase capacity of
the motor and driver and slow down
deceleration time. Use an external
regenerative resistor.

(2) Check an operating pattern (waveform graphic).

Check the load factor of the regenerative resistor
and display of over-regeneration warning. Increase
capacity of the motor and driver and slow down
deceleration time. Reduce rotation speed of the
motor. Use an external regenerative resistor.

(3) Set Pr6c to 2.

Connect the encoder cable as per the wiring
diagram. Correct wrong connections of the
connector pins, if any.

Time (sec)

Overload Protection Time-limiting Characteristics

100

100 115

150

200

250

300

350

400

450

Torque (%)

10

1

MUMA 50W, 100W
MUMA 200W, 400W

<Note> When you set Pr6C to 2, be sure to install an external safeguard such as a temperature

fuse, etc.
Otherwise, protection of regenerative resistor is lost, causing abnormal heat generation and
burnout of the regenerative resistor.