5-3

IM 04P01B01-01E

Frequently

Used

Setup

Operat

ons
(Sett

ng

Mode)

5.1 Settng the Input Range

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

Lnear Scalng

Select Scale.

Set the channel range.

Select Volt, TC, RTD, or DI.

Select the range type.

Set the left span value.

Set the right span value.

Set the decimal position

and left scale value.

Set the right scale value.

The new setting takes effect.

First channel Last channel

ESC/?

Set=Range

CH=01-01

Mode=Scale

Type=Volt

Range=2V

Span_L= -2.000

Span_R= 2.000

Scale_L= 0.00

Scale_R= 200.00

01-01 Channel

Setting complete

Descrpton

• Scale Left, Scale Rght, and Decmal Poston

Selectable range (mantissa): –20000 to 30000
Example: The value in the range of –100.00 to 350.00 cannot be specified. The

mantissa of Scale_R is 35000, which exceeds the upper limit of 30000. Set
in the range of –100.0 to 350.0.

Decimal position: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX
The decimal position is set using Scale_L. It cannot be set using Scale_R.
Example: Change 0.00 to 0.0.

Press the

key to move the cursor to the last digit of 0.00.

Space

Press the key to change the value to 0.0 .

Note

The displayable/printable range of scale values is –19999 to 30000 excluding the decimal.

<Related Topcs> Setting the unit: Section 5.3