6.10 Settng the Alarm Delay Duraton

This section explains the details of setting the duration of the delay alarm.

Procedure

1.

Hold down the

MENU

key for 3 seconds to enter Setting mode.

2.

Press the

key or

SHIFT +

key to select

Aux and then press the key.

3.

Press the

key or

SHIFT +

key to select

Alm delay T and then press the

key.

4.

Set each item and press the key.

Use the

key or

SHIFT +

key to select values.

For the procedure on how to enter values or characters, see section 4.2.
If you press the

ESC key in the middle of the operation, the settings entered up to

then are cancelled, and the display returns to a higher level menu.

5.

When the

Settng complete screen appears, do either of the following:

Press the key to set other channels.
If you are done, press the

ESC key.

6.

Hold down the

MENU

key for 3 seconds to return to Operation mode.

Set the channel range.

Set the alarm delay time.

The new setting takes effect.

ESC/?

First channel Last channel

Set=Aux

Aux=Alm delay T

CH=01-01

Duration= 10

01-01 Channel

Setting complete

Explanaton

Duraton

The duration can be set to a value in the range of 1 to 3600 s.
However, if the scan interval on the dot model is 2.5 s, the actual duration is an integer
multiple of 2.5 s. If the set value is not equal to an integer multiple of 2.5 s, the duration is
the smallest integer multiple of 2.5 s greater than the set value.
Example: The actual duration for 1 s and 2 s is 2.5 s.

<Related Topcs> Enabling the alarm delay function: Section 7.15