7.3 Settng the Burnout Detecton Functon of

Thermocouples

This section explains the details of setting the burnout detection function of
thermocouples to channels set to 1-5V or TC input.
Basic Setting mode cannot be entered when recording is in progress or when
computation is in progress on models with the computation function (/M1 option).

Procedure

Changng the Settngs

1.

Hold down the

MENU

key for 3 seconds to enter Setting mode.

2.

Hold down the

and

keys simultaneously for 3 seconds to enter Basic

Setting mode.

3.

Press the

key or

SHIFT +

key to select

Burnout and then press the

key.

4.

Set each item and press the key.

Use the

key or

SHIFT +

key to select values.

For the procedure on how to enter values or characters, see section 4.2.
If you press the

ESC key in the middle of the operation, the settings entered up to

then are cancelled, and the display returns to a higher level menu.

5.

When the

Settng complete screen appears, do either of the following:

Press the key to set other channels.
If you are done, press the

ESC key.

Set the channel range.

The new setting takes effect.

Select the recording operation that is

carried out when a burnout is detected.

ESC/?

First channel Last channel

01-01 Channel

Setting complete

Basic=Burnout

CH=01-01

Burnout=Off

Applyng the Changes and Returnng to Operaton Mode

Press the

key or

SHIFT +

key to select

End and then press the key. Press

the

key to select

Store and then press the key. The changes are applied, and

the screen returns to Operation mode. If you select

Abort and press the key, the

changes are discarded, and the screen returns to Operation mode. Press the

ESC key to

return to the

Basc= screen.

Explanaton

Burnout

Selects the action taken when a burnout is detected at the 1-5V input or the
thermocouple input.
Up: Records off the scale on the 100% side.
Down: Records off the scale on the 0% side.
Select Off when not using the burnout detection function.