Yokogawa µR10000 User Manual

Page 34

Advertising
background image

IM 04P01B01-01E

1-18

For the procedure to set the functions, see section 1.10, “Function Setup Guide.”

Alarm Prntout

Alarm information is printed when an alarm occurs or releases.
Printout is not performed when the chart speed is as follows:
Pen model: 1600 mm/h or higher, dot model: 101 mm/h or higher

Time of alarm occurrence/release

Indicates that there are alarms that are not

printed because the alarm printout buffer is full.

Level number

Alarm type

Channel number or tag

: Alarm occurrence, : Alarm release

• The print condition can be set to (1) print when alarms occur and release, (2) print

only when alarms occur, or (3) do not print.

• Alarms that occur while an alarm printout is in progress are temporarily saved to the

buffer memory in a printout-wait condition. Alarms are cleared from the buffer memory
when they are printed.

• The number alarms that can be stored in the buffer is 8 and 12 on the pen model and

dot model, respectively. Alarms that occur while the buffer is full are not printed. A
buffer overflow mark is printed when there are alarms that cannot be printed because
the buffer is full.

• The time printout format can be selected.

Type

Prntout format

Type

Prntout format

Hour:Minute

10 : 00

Hour:Minute:Second

10 : 00 : 00

Month:Day:

Hour:Minute

Nov. 09

10 : 00

Month:Day:

Hour:Minute:Second

Nov. 09

00 : 00 : 00

Year:Month:Day:

Hour:Minute:Second

Nov. 09. 2004

10 : 00 : 00

* The format of year, month, and day varies depending on the setting (see the next page).

Perodc Prntout

Measured values and other items are printed at the preset interval.
Printout is not performed when the chart speed is as follows:
Pen model: Less than or equal to 9 mm/h or greater than or equal to 1600 mm/h
Dot model: 9 mm/h or less, 101 mm/h or greater

• Prntout Contents (for detals, see appendx 1)

• Date/time, time ticks (marks that indicate the positions of the date/time on the chart

paper); measured values, alarm status, scale (leftmost and rightmost values of
span) and recording color (pen model) for each channel; and chart speed can be
printed. When pen offset is being executed on the pen model, the pen offset marks
are printed. On the pen model, if a time tick is not printed at the correct position, a
time tick cancel mark (!) is printed.

• Printout of measured values and alarm status can be enabled or disabled for each

channel.

• Printout of the scale and recording colors (pen model) can be enabled or disabled.

The scale can be printed when the recording zone is greater than or equal to 40 mm.

• The measured values for each channel can be selected from the following data types.
Instantaneous value (measured value at the time of periodic printout)
AVE (average of the measured values over an interval)
MIN (minimum value of the measured values over an interval)
MAX (maximum value of the measured values over an interval)
MIX (minimum , maximum , and average value of the measured values over an interval)
SUM (summed value of the measured values over an interval)

• Interval (for detals, see appendx 2)

The printout interval can be set by specifying the value or set automatically in sync

with the chart speed.

1.4 Recordng

Advertising