IM 04P01B01-01E

2-10

Wrng Procedure

1.

Turn OFF the recorder and remove the terminal cover.

2.

Connect the input/output signal wires to the terminals.

Philips

screwdriver

Crimp-on lug with

insulation sleeves

3.

Replace the terminal cover and fasten it with screws.

The proper torque for tightening the screws is 0.6 N•m.

Alarm Output Relay Termnals and FAIL/Chart End Output Relay Termnals

C

NO

NC

NO (Normally Opened), C (Common), NC (Normally Closed)

• Relay Contact Output Specfcatons

Output type:

Relay

Contact rating:

250 VAC (50/60 Hz)/3 A, 250 VDC/0.1 A (resistive load)

Dielectric strength:

1500 VAC at 50/60 Hz for one minute (between output
terminals and the ground terminal)

Remote Control Input Termnals

1

2

3

4

5

C

1

2

3

4

5

C

C

1 to 5

Internal circuit

Input type:

Photocoupler isolation

Shared common (C)

Allowable input voltage:

5 VDC

5V

1 to 5 (Remote control input terminals), C (Common)

Transistor input

(open collector)

Relay contact input

(voltage-free contact)

• Relay Contact Input/Transstor Input Specfcatons

Input signal:

• Voltage-free contact: Contact closed at 200 Ω or less and

contact open at 100 kΩ or greater

• Open collector: 0.5 V or less (30 mADC) when turned ON,

leakage current of 0.25 mA or less when turned OFF

Dielectric strength:

500 VDC for one minute between input terminals and the
ground terminal

Note

To reduce noise, use a shielded cable for the wiring of the remote control input terminals.
Connect the shield to the ground terminal of the recorder.

2.4 Optonal Termnal Wrng