IM 04P01B01-01E

5-6

5.1 Settng the Input Range

1-5V Input

Select 1-5V.

Set the channel range.

Set the left span value.

Set the right span value.

Set the decimal position

and left scale value.

Set the right scale value.

Turn On or Off the low-cut function.

The new setting takes effect.

First channel

(When low-cut is set to Use)

Last channel

ESC/?

Set=Range

CH=01-01

Mode=1-5V

Span_L= 1,000

Span_R= 5,000

Scale_L= 0.00

Scale_R= 200.00

Low-cut=Off

01-01 Channel

Setting complete

Descrpton

• Span Left and Span Rght

Selectable span left range: 0.8 to 1.2 V
Selectable span right range: 4.8 to 5.2 V

• Scale Left, Scale Rght, and Decmal Poston

Selectable range (mantissa): –20000 to 30000
Example: The value in the range of –100.00 to 350.00 cannot be specified. The

mantissa of Scale_R is 35000, which exceeds the upper limit of 30000. Set
in the range of –100.0 to 350.0.

Decimal position: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX
The decimal position is set using Scale_L. It cannot be set using Scale_R.
Example: Change 0.00 to 0.0.

Press the

key to move the cursor to the last digit of 0.00.

Space

Press the key to change the value to 0.0 .

Make sure that scale left is less than scale right.

• Low-cut

On: Cuts values below 0% of the recording span (set to 0% (scale left value)).
Off: Does not apply the low-cut function.

<Related Topcs> Setting the unit: Section 5.3

Enabling the low-cut function: Section 7.15