IDEX Health & Science VS-606V7 Series User Manual

Page 102

Advertising
background image

102

Storing parameters [Enter command] (can be written only.)

When a parameter is written from the PLC by communications, the parameter is
written to the parameter data area on the RAM in the VS-606V7. ENTER command is
a command to write the parameter data on the RAM to the non-volatile memory in the
VS-606V7. Writing data (can be undefined) to register number 0900H during stop
executes this ENTER command.

Maximum number of writing times of the non-volatile memory used for VS-606V7 is
100,000; do not execute the ENTER command excessively. When a parameter is
changed from the digital operator, the parameter data on the RAM is written to the non-
volatile memory without ENTER command.

Register number 0900H is used only for write-in. If this register is readout, register
number error (error code: 02H) occurs.

Register

Number

Name

Contents

Setting Range

Default

0900H

ENTER

command

Write-in parameter data to non-

volatile memory (EEPROM).

0000H to FFFFH

-