Frequency Reference by Pulse Train Input

Frequency reference can be set by pulse train input from the multi-function input
terminal.

Input pulse specifications

Low-level voltage: 0.8V or less

High-level voltage: 3.5 to 32V

Duty Cycle: 30 to 70%

Pulse frequency: 0 to 33 kHz

Frequency reference method
Frequency reference is a value obtained by multiplying the ratio of the maximum
input pulse frequency and actual input pulse frequency by the maximum output
frequency.

Parameter

No.

Name

Unit

Setting range

Initial Setting

n003

Run command selection

1

0 to 2

0

n004

Frequency reference selection

1

0 to 6

0

n149

Pulse train input scaling 1=10Hz

1

100 to 3300

(33kHz)

2500

(25kHz)

Reference freq

Input pulse frequency

Minimum pulse train frequency (n149)

10

×

-----------------------------------------------------------------------------------------------------------------

max output frequency (n011)

×

=

Run/stop and FWD/REV can
be selected by a switch
connected to the control circuit
terminal.

Frequency setting can be set
by pulse train input signal [0 to
100% (maximum frequency)/0
to 33kHz] connected to the
multi-function input terminal.