Multi-function output terminal MA, MB, P1 and P2 functions can be changed when
necessary by setting parameters n057, n058, and n059.

Terminal MA and MB functions: Set to n057

Terminal P1 function: Set to n058

Terminal P2 function: Set to n059

Using output signals (n057, n058, n059)

Setting

Name

Description

Ref page

0

Fault

Closed when inverter fault occurs.

1

In operation

Closed when either FWD/REV command is input or
voltage is output from the inverter.

2

Agreed frequency

Closed when setting frequency agrees with inverter
output frequency.

79

3

Zero speed

Closed when inverter output frequency is less than
minimum output frequency.

4

Frequency detection

Output frequency

frequency detection level (n095)

56

5

Frequency detection

Output frequency

frequency detection level (n095)

56

6

Overtorque detection
(NO contact output)

55

7

Overtorque detection
(NC contact output)

55

10

Minor Fault

Closed when the alarm is indicated.

11

Base blocked

Closed when the inverter output is shut off.

12

Operation mode

Closed when “LOCAL” is selected by LOCAL/REMOTE
selection.

13

Inverter operation ready

Closed when inverter fault is not detected, and
operation is ready.

14

Fault restart

Closed during fault retry

15

In UV

Closed when undervoltage is detected.

16

In reverse run

Closed during reverse run.

17

In speed search

Closed when inverter conducts speed search.

18

Data output from
communication

Operates multi-function output terminal independently
from inverter operation (by MEMOBUS
communication).

89

19

PID feedback loss

Closed during PID feedback loss

109

20

Frequency reference is
missing

Closed when frequency reference is missing

21

Inverter overheat prediction
OH3

Closed when overheat prediction is input. Digital
operator display is “OH3 (blinking).”