Operating (RUN /STOP commands) by communications

Setting parameter n003 to 2 in REMOTE mode can give RUN / STOP commands
by communication (MEMOBUS communications). For the command by
transmission, refer to page 89).

Selecting Frequency Reference

Frequency reference can be selected by the following methods.

Setting by operator

Select REMOTE or LOCAL mode in advance. For the method of selecting the
mode, refer to page 44.

LOCAL mode

Select command method by parameter n008.
n008 =0 : Enables the setting by potentiometer on digital operator.

=1 : Enables the digital setting by digital operator. (Initial Setting)

Factory setting of the model with digital operator (with
potentiometer) JVOP-140 is n008=0.

• Digital setting by digital operator

Input frequency while FREF is lit (press ENTER after setting the numeric value).

Frequency reference setting is effective when 1 (initial setting : 0) is set to
parameter n009 instead of pressing ENTER key.
n009 =0 : Enables frequency reference setting by ENTER key.

=1 : Disable frequency reference setting by ENTER key.

REMOTE mode

Select command method by parameter n004.
n004 =0 : Enables frequency reference setting by potentiometer on digital

operator.

=1 : Frequency reference 1 (n024) is effective (Initial setting)

Factory setting of the model with digital operator (with potentiometer)
JVOP-140 is n004=0

=2 : Voltage reference (0 to 10V) (See the figure on page 47)

=3 : Current reference (4 to 20mA) (Refer to page 81)

=4 : Current reference (0 to 20mA) (Refer to page 81)

=5 : Pulse train reference (Refer to page 82)

=6 : Communication (Refer to page 90)

=7 : Voltage reference of digital operator circuit terminal (0-10)

=8 : Current reference of digital operator circuit terminal (4-20mA)

=9 : Communication card (optional)