IDEX Health & Science VS-606V7 Series User Manual

Page 131

Advertising
background image

131

Blinking

Warning

Fault contacts
do not change
state.

OP

(parameter setting error

when the parameter setting is
performed through the
MEMOBUS communications)
OP1: Two or more values are

set for multi-function
input selection.
(parameters n050 to
n056)

OP2: Relationship among

V / f parameters is not
correct.
(parameters n011,
n013, n014, n016)

OP3: Setting value of motor

rated current exceeds
150% of inverter rated
current. (parameter
n036)

OP4: Upper/lower limit of

frequency reference is
reversed. (parameters
n033, n034)

OP5: (parameters n083 to

n085)

Check the setting
values.

Blinking

OL 3 (Over torque detection)
Motor current exceeded the
preset value in parameter
n098.

Reduce the load and
expand the accel/decel
time.

Blinking

SER (Sequence error)
Inverter receives LOCAL/
REMOTE select command or
communication/control circuit
terminal changing signals
from the multi-function
terminal while the inverter is
outputting.

Check the external
circuit (sequence).

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN (Green)

ALARM (Red)

Advertising