Pid output gain (n163), Pid feedback value adjusting gain (n129) – IDEX Health & Science VS-606V7 Series User Manual

Page 113

Advertising
background image

113

PID Output Gain (n163)

This parameter adjusts the output gain.

PID Feedback Value Adjusting Gain (n129)

Parameter n129 is the gain that adjusts the feedback value.

PID Feedback Loss Detection (n136, n137, n138)

Parameter

No.

Name

Unit

Setting

Range

Initial

Setting

n163

PID Output gain

Multiples

0.0 to 25.0

1.0

Parameter

No.

Name

Unit

Setting

Range

Initial

Setting

n129

PID feedback value

adjusting gain

Multiples

0.0 to 10.0

1.00

Parameter

No.

Name

Unit

Setting

Range

Initial

Setting

n136

Selection of PID
feedback loss detection

-

0: No detection of PID

feedback loss

1: Detection of PID

feedback loss
(Operation

continued: FbL
alarm)

2: Detection of PID

feedback loss

(Output shut down:
fault)

0

n137

PID feedback loss
detection level

%

0 to 100

100%/Max. output

frequency

0

n138

PID feedback loss
detection time

%

0.0 to 25.5

1.0

Advertising