IDEX Health & Science VS-606V7 Series User Manual

Page 54

Advertising
background image

54

*When “deceleration to a stop” is selected (n005=0).

By setting “Multifunction Input Selection” (either of n050 to n056) to “11 (accel/decel
time select)”, accel/decel time is selected by turning ON/OFF the accel/decel time
select (terminal S1 to S7).
At OFF : n019 (accel time 1)

n020 (decel time 1)

At ON : n021 (accel time 2)

n022 (decel time 2)

Adjusting frequency upper and lower limits

Frequency reference upper limit (n033)
Sets the upper limit of the frequency
reference in units of 1%.
(n011: Maximum output frequency = 100%)
Factory setting: 100%

Frequency reference lower limit (n034)
Sets the lower limit of the frequency
reference in units of 1%.
(n011: Maximum output frequency = 100%)
When operating at frequency reference 0,
operation is continued at the frequency
reference lower limit.
However, when frequency reference lower
limit is set to less than the minimum output
frequency (n016), operation is not performed.
Factory setting: 0%

Using two accel/decel times

Advertising