Motor Overload Protection

Electronic thermal overload relay

Instantaneous Over Current

Motor coasts to a stop at approx. 250% of inverter rated
current

Overload

Motor coasts to a stop after 1 minute at 150% of inverter
rated output current

Over Voltage

Motor coasts to a stop if DC bus voltage exceed 820V

Under Voltage

Stops when DC bus voltage is approx. 400V or less

Momentary Power Loss

Following items are selectable: Not provided (stops if
power loss is 15ms or longer), continuous operation if
power loss is approx. 0.5s or shorter, continuous operation

Cooling Fin Overheat

Protected by electronic circuit

Stall Prevention Level

Can be set to individual levels during accel/decel,
provided/not provided available during coast to a stop

Cooling Fan Fault

Protected by electronic circuit (fan lock detection)

Ground Fault

Protected by electronic circuit (over current level)

Power Charge Indication

ON until the DC bus voltage becomes 50V or less.

Other

Functions

Input

S

ignal

s

Multi-function Input

Seven of the following input signals are selectable:
Forward/reverse run (3-wire sequence), fault reset,
external fault (NO/NC contact input), multi-step speed
operation, Jog command, accel/decel time select, external
baseblock (NO/NC contact input), speed search
command, accel/decel hold command, LOCAL/REMOTE
selection, communication/control circuit terminal selection,
emergency stop fault emergency stop alarm, UP/DOWN
command, self-test, PID control cancel, PID intregal reset/
hold

O

u

tp

ut

S

ignal

s

Multi-function Output

Following output signals are selectable (1 NO/NC contact
output, 2 photo-coupler outputs): Fault, running, zero
speed, at frequency, frequency detection (output
frequency

or

set value), during over torque detection,

during under voltage detection, minor error, during
baseblock, operation mode, inverter run ready, during fault
retry, during UV, during speed search, data output through
communication, PID feedback loss detection

Standard Functions

Voltage vector control, full-range automatic torque boost,
slip compensation, DC injection braking current/time at
start/stop frequency reference bias/gain, MEMOBUS
communications (RS-485/422, max. 19.2K bps), PID
control, energy-saving control, parameter copy, frequency
reference with built-in potentiometer, Unit selection for
frequency reference setting/display

*

The protection functions at approximately 50% of inverter rated output

current.

Voltage Class

400V 3-phase

Model

CIMR-V7*C

‰‰‰‰

3-phase

40P2 40P4 40P7 41P5 42P2 43P0 43P7 45P5 47P5

Single-phase