126

Notes:

1. The frequency reference parameters and monitor display data for which this

selection of unit function is valid, are stored in the inverter in units of Hz.

The units are converted as follows.

2. The upper limit for each unit is the figure whose fractions below the significant

digits are cut off.

(Example) Where the upper limit value for the unit Hz is 60.00 Hz and n035 = 39,

120 x 60.00 Hz ÷ 39 = 184.9, accordingly 184 r/min is displayed for the

upper limit value.

For the displays other than upper limit value, the fractions below the significant
digits are rounded.

3. To execute VERIFY for parameter COPY function, frequency reference parameters

(in units of Hz) is applied.

Parameter

n035

Setting

Description

40
to

3999

• Set the display value at 100% of frequency reference (set value of Fmax(n011))
at 1st to 4th digit of n035.
By a number of 4th digit of n035, set the position of decimal point.
By 1st to 4th digit of n035, set a 3-digit figure excluding decimal point.
Number of 4th digit. Position of decimal point 40 to 3999

0
1
2
3 0.
(Example) To display 20.0 at 100% of frequency reference, set n035 to “1200.”
• Setting range
min{(Lower 3-digits of n035) x Frequency reference lower limit (n034) to (Lower 3-digits

of n035) x Frequency reference upper limit (n033), 400Hz (Lower 3-digits of n035) to
Fmax(n011), 999}

Max. upper limit value: (Set value ÷ (Lower 3-digits of n035)) x Fmax(n011)< 400Hz

Setting/Display

parameter n035

Frequency reference parameters

Data for monitor d

isplay

Display

Setting


system

Each unit

Units of Hz