Surge suppressors

Ground fault interrupter:
Select a ground fault interrupter not affected by high frequencies. To prevent
malfunctions, the current should be 200mA or more and the operating time 0.1 sec.
or more.
Example:• NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988 and

after)

• EGSG series by Fuji Electric Co., Ltd. (manufactured in 1984 and after)

AC and DC reactor:
Install an AC reactor to connect to a power supply transformer of large capacity
(600kVA or more) or to improve power factor on the power supply side.

Noise filter:
Use a noise filter exclusively for inverter if radio noise generated from the inverter
causes other control devices to malfunction.

For the details of the peripheral devices, refer to the catalog.

Parameter List

Addition of parameters accompanied by the upgraded software version

The parameters marked with #1 and #2 are applicable for the following upgraded
software version Nos.:

#1: Applicable for software version No. VSP 010015 or later

#1: Applicable for software version No. VSP 010020 or later

Parameters that can be changed during operation

The parameters whose numbers are in bold can be changed during operation.

Model

DCR2-

Specifications

Code No.

200V

to

230V

Large size magnetic contactors

50A22E

250VAC

0.5

µ

F 200

C002417

Control relays
MY-2, -3 (OMRON)
HH-22, -23 (FUJI)
MM-2, -4 (OMRON)

10A25C

250VAC

0.1

µ

F 100

C002482

NOTE

(1) Never connect a general LC/RC noise filter to the inverter output circuit.

(2) Do not connect a phase advancing capacitor to the I/O sides and/or a surge

suppressor to the output side.

(3) When a magnetic contactor is installed between the inverter and the motor,

do not turn it ON/OFF during operation.

Surge Suppressors

Coils and relays