124

Display List

Note: While rEd, CPy, or vFy is displayed by blinking, key input on the digital operator is disabled.

While rEd, CPy and vFy are not displayed by blinking, pressing DSPL or ENTER redisplays the

parameter No.

Operator

display

Description

Corrective action

Lit: Setting for parameter copy function
selection enabled

-

Lit: READ selected
Flashed: READ under execution

-

Lit: Writing (COPY) selected
Blinks: Writing (COPY) under execution

-

Lit: VERIFY selected
Flashed: VERIFY under execution

-

Lit: Inverter capacity display selected

-

Lit: Software No. Display selected

-

Lit: READ, COPY (writing), or VERIFY
completed

-

Blinks: Attempt to execute READ while
Parameter Read Prohibited Selection (n177) is
set to 0.

Confirm the necessity to execute READ, then
set parameter Read Prohibited selection (n177)
to 1 to execute READ.

Blinks: The parameter could not be read
properly by READ operation. Or, a main circuit
low voltage is detected during READ operation.

Confirm that the main circuit power supply
voltage is correct, then re-execute READ.

Blinks: A sumcheck error occurs in the
parameter data stored in the digital operator.

The parameter stored in the digital operator
cannot be used.
Re-execute READ to store the parameters in
the digital operator.

Blinks: The password for the connected
inverter and that for the parameter data stored
in the digital operator do not agree.
[EX.]Writing (Copy) from VS-606V7 to Vsmini
J7

Check if they are the same product series

Blinks: No parameter data stored in the digital
operator.

Execute READ

Blinks: Attempt to execute writing (COPY) or
VERIFY between different voltage classes or
different control modes

Check each voltage class and control mode.

Blinks: A main circuit low voltage is detected
during writing (COPY) operation.

Confirm that the main circuit power supply
voltage is correct, then re-execute writing
(COPY).

Lit: A sumcheck error occurs in the parameter
data stored in the inverter.

Initialize the parameters. If an error occurs
again, replace the inverter due to a failure of
parameter memory element (EEPROM) in the
inverter.

Blinks: Attempt to execute VERIFY between
different inverter capacities.

Press ENTER to continue the execution of
VERIFY. Press STOP to interupt the execution
of VERIFY.

Blinks: A communication error occurs between
the inverter and the digital operator.

Check the connection between the inverter and
the digital operator.
If a communication error occurs during READ
operation or writing (COPY) operation, be sure
to re-execute READ or COPY.