Performing self-test

VS-606V7 is provided with a function to perform self-diagnosis for operation check of
the serial communication I/F circuit. This function is called self-test. In the self-test,
connect the sending terminal with the receiving terminal in the communication section.
It assures if the data received by VS-606V7 is not being changed. It also checks if the
data can be received normally. Carry out the self-test in the following procedure.

(1) Turn ON the VS-606V7 mini power supply. Set parameter n056 to 35 (self-test).

(2) Turn OFF the VS-606V7 mini power supply.

(3) Make the following wiring with the power supply turned OFF.

(4) Turn the power ON.

Normal operation: Operator displays frequency reference value.

Faulty operation: Operator displays “

”, fault signal is turned ON and inverter ready

signal is turned OFF.