Protective
Operation

Output is shut
OFF and motor
coasts to a
stop.

EF

(External fault)
Inverter receives an external
fault input from control circuit
terminal.
EF0: External

fault

reference

through MEMOBUS
communications

EF1: External fault input

command from control
circuit terminal S1

EF2: External fault input

command from control
circuit terminal S2

EF3: External fault input

command from control
circuit terminal S3

EF4: External fault input

command from control
circuit terminal S4

EF5: External fault input

command from control
circuit terminal S5

EF6: External fault input

command from control
circuit terminal S6

EF7: External fault input

command from control
circuit terminal S7

Check the external
circuit (sequence).

CPF-00
Inverter cannot communicate
with the digital operator for 5
sec. or more when power is
turned ON.

Cycle power after
checking the digital
operator is securely
mounted.
If the fault remains,
replace the digital
operator or inverter.

CPF-01
Transmission fault occurred
for 5 sec. or more when
transmission starts with the
digital operator.

Cycle power after
checking the digital
operator is securely
mounted.
If the fault remains,
replace the digital
operator or inverter.

CPF-04
EEPROM fault of inverter
control circuit is detected.

• Record all parameter

data and initialize the
parameters. (Refer
to page 32 for
parameter
initialization)

• Cycle power.

If the fault remains,
replace the inverter.

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN (Green)

ALARM (Red)