IDEX Health & Science VS-606V7 Series User Manual
Page 70
70
(3) Set carrier frequency (n080) to either 1, 2, 3, 4 when using vector con-
trol mode. Do not set to 7, 8, or 9.
(4) Carrier frequency is automatically reduced to 2.5kHz when reducing
carrier frequency selection at low speed (n175) is set to 1 and the fol-
lowing conditions are satisfied:
Output frequency < 5 Hz
Output current > 110%
Factory setting : 0 (Disabled)
Selects processing when STOP key is pressed during operation either from multi-func-
tion input terminal or communications.
Operator stop key selection (n007)
Setting
Description
0
STOP key effective when running either from multi-function input terminals or communications.
When STOP key is pressed, the inverter stops according to the setting of the parameter n005.
At this time, the digital operator displays “ “ alarm (blinking). This stop command is held in
the inverter until both forward and reverse run commands are open, or until run command from
communications becomes zero.
1
STOP key is ineffective when running either from multi-function input terminals or
communications.