< Corrective Actions of models with digital operator >

Alarm Display and Contents

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN (Green)

ALARM (Red)

Blinking

Warning

Fault contacts
do not change
state.

UV (Main circuit low voltage)
Main circuit DC voltage drops
below the low-voltage
detection level while the
inverter output is OFF.
200V: Stops at main circuit

DC voltage below
approx. 200V (160V for
single phase)

400V:Stops at main circuit DC

voltage below approx.
400V.

(Control supply fault) Control
power supply fault is detected
while the inverter output is
OFF.

Check the following:
• Power supply

voltage

• Main circuit power

supply wiring is
connected.

• Terminal screws are

securely tightened.

Blinking

OV (Main circuit over voltage)
Main circuit DC voltage
exceeds the over voltage
detection level while the
inverter output is OFF.
Detection level:
200V class: Approx 410V or
more
400V class: Approx 820V or
more

Check the power
supply voltage.

Blinking

OH (Cooling fin overheat)
Intake air temperature rises
while the inverter output is
OFF.

Check the intake air
temperature.

Blinking

OH3(Inverter overheating pre-
alarm)* signal is input.

Release the input of
inverter overheating
pre-alarm signal.

Blinking

CAL (MEMOBUS
communications waiting)
Correct data has not been
received from the PLC when
the parameters n003
(operation command
selection) is 2 or n004
(frequency reference
selection) is 6, and power is
turned ON.

Check communication
devices and
transmission signals.

: ON

: Blinking

: OFF

*Display only applies to 200/400V class. 7.5/10hp(5.5/7.5kW) inverters.