Selecting run/stop commands – IDEX Health & Science VS-606V7 Series User Manual

Page 47

Advertising
background image

47

Selecting Run/Stop Commands

Refer to Switching LOCAL/REMOTE Modes (Page 44) to select either the
LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run commands) can be
selected by the following method.

LOCAL Mode

When Lo (local mode) is selected by digital operator

ON mode, or

when the LOCAL / REMOTE switching function is set and the input terminals are

turned ON, run operation is enabled by the

or

of the digital operator,

and FWD/REV run is selected by

ON mode (using

or

key).

REMOTE mode

Select remote mode.
The following two methods are used to select remote mode:

1. Select rE (remote mode) by

selection.

2. When the local / remote switching function is selected by multi-function

input selection, turn OFF the input terminal to select remote mode.

Select operation method by setting the parameter n003.
n003 =0: Enables the digital operator (same with local mode)

=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications

=3: Enables communication card (optional)

Example for using the multi-function input terminal as operation reference
(two-wire sequence)

Below shows the example of three-wire sequence, (Refer to page 70.)

For example of three-wire sequence, refer to page 70

Note:

When inverter is operated without the digital operator, always set the
parameter n010 to 0.

)

Advertising