Wire and terminal screw sizes – IDEX Health & Science VS-606V7 Series User Manual

Page 23

Advertising
background image

23

• Wire and Terminal Screw Sizes

1. Control Circuit

2. Main Circuit

200V Class 3-phase Input Series

Note:

The wire size is set for copper wires at 160

°

F (75

°

C)

Model

Terminal Symbol

Screw

Tightening

Torque

lb • in (N • m)

Wire

Applicable size

Recommend

size

Type

mm

2

AWG

mm

2

AWG

Common

to

all models

MA, MB, MC

M3

4.44 to 5.33

(0.5 to 0.6)

twisted wire 0.5 to 1.25
single

0.5 to 1.25

20 to 16
20 to 16

0.75

18

Shielded

wire or

equivalent

S1 to S7,P1, P2,SC,PC,R+,

R-,S+,S-

,FS,FR,FC,AM,AC,RP

M2

1.94 to 2.21

(0.22 to 0.25)

twisted wire 0.5 to 0.75
single

0.5 to 1.25

20 to 18
20 to 16

0.75

18

Model

Terminal Symbol

Screw

Tightening

Torque

lb • in

(N • m)

Wire

Applicable

size

Recommended

size

Type

mm

2

AWG

mm

2

AWG

CIMR-V7AA20P1

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M3.5

7.1 to 8.88
(0.8 to 1.0)

0.75 to 2

18 to

14

2

14

600V
vinyl-

sheathed

wire or

equivalent

CIMR-V7AA20P2

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M3.5

7.1 to 8.88
(0.8 to 1.0)

0.75 to 2

18 to

14

2

14

CIMR-V7AA20P4

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M3.5

7.1 to 8.88
(0.8 to 1.0)

0.75 to 2

18 to

14

2

14

CIMR-V7AA20P7

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M3.5

7.1 to 8.88
(0.8 to 1.0)

0.75 to 2

18 to

14

2

14

CIMR-V7AA21P5

R/L1,S/L2,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M4

10.65 to 13.31

(1.2 to 1.5)

2 to 5.5

14 to

10

2

14

CIMR-V7AA22P2

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M4

10.65 to 13.31

(1.2 to 1.5)

2 to 5.5

14 to

10

3.5

12

CIMR-V7AA24PO

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M4

10.65 to 13.31

(1.2 to 1.5)

2 to 5.5

14 to

10

5.5

10

CIMR-V7*A25P5

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M5

22.19

(2.5)

5.5 to 8 10 to 8

8

8

CIMR-V7*A27P5

R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3

M5

22.19

(2.5)

5.5 to 8 10 to 8

8

8