Operating the inverter, Test run – IDEX Health & Science VS-606V7 Series User Manual

Page 28

Advertising
background image

28

5. OPERATING THE INVERTER

Initial setting of control mode selection (n002) is set at V/f control mode.

Test Run

The inverter operates by setting the frequency (speed).

There are three types of operation modes for the VS-606V7:

1. Run command from the digital operator (local potentiometer/digital setting).

2. Run command from the control circuit terminal.

3. Run command from communications (MEMOBUS communications).

Prior to shipping, the drive is set up to receive run command and frequency reference
from the operator. Below are instructions for running the VS-606V7 using the digital
operator JVOP-140 (with local potentiometer) or optional JVOP-147 (without local
potentiometer. For instructions on operation, refer to page 37.

Operation reference or frequency reference parameters can be selected separately as
shown below.

Name

parameter

Operation Reference

Selection

N003 = 0 --- Enables operator RUN, STOP/RESET

= 1 --- Enables control circuit terminal run/stop

= 2 --- Enables communications (MEMOBUS communications)

= 3 --- Enables communication card (optional)

Frequency Reference

Selection

N004 = 0 --- Enables digital operator potentiometer

= 1 --- Enables frequency reference 1 (parameter 024)

= 2 --- Enables voltage reference (0 to 10V) of control circuit terminal

= 3 --- Enables current reference (4 to 20mA) of control circuit terminal

= 4 --- Enables current reference (0 to 20mA) of control circuit terminal

= 5 --- Enables pulse line reference of control circuit terminal

= 6 --- Enables communications (MEMOBUS communications)

= 7 --- Enables voltage reference (0 to 10V) of operator circuit terminal

= 8 --- Enables current reference (4 to 20 mA) of operator circuit terminal

= 9 --- Enables communication card (optional)