Figure 4-10 select output screen -29, Figure 4-11 program output screen -29 – INFICON MDC-360C Thin Film Deposition Controller User Manual

Page 69

Advertising
background image

MDC-360C DEPOSITION CONTROLLER

PROGRAMMING AND CONTROLLER SETUP

4-29

Two screens are required to program the Discrete outputs. The first screen
provides for selecting the output to be programmed, while the second screen
provides for the actual programming, including the output name.

Selecting Program Outputs from the System Setup menu will present the Select
Output screen.

Figure 4-10 Select Output screen

Selecting an output with the Right-arrow or Enter key will present the screen
which permits definition of the output, as shown below.

The Left-arrow, Right-arrow, Up-arrow and Down-arrow keys provide access to
the Output Name, card#, pin# and Condition string edit fields. A 16-digit name
can be assigned to the logical input. Any entry other than 1 or 2 will be ignored
for the card#, as will a pin# less than 2 or greater than 9.

Figure 4-11 Program Output Screen

The output condition string is a logical statement that determines the state of the
output. The output relay is closed when the condition string is evaluated as true.
Otherwise, the relay is open. Each output condition string is evaluated ten times
per second (every 100 milliseconds).

Select Output

01

End of Process

-

02 Wire feed Al

03 Layer Complete

04 Procs Complete

05

06
07
- View/Edit 08

’

Card# Pin#-Rt
Output Name

Wire Feed Al

------- 1 2 21

Conditions Al & FeedHold


Valid operators: 1=!, 2=(, 3=), 4=&, 5=|
Press 0 for conditions, to validate.

Advertising