Technical data, General data and operating conditions – Lenze E82EV 8200 User Manual

Page 100

Advertising
background image

Technical data

General data and operating conditions

3

l

100

EDK82EV113 DE/EN/FR 11.0

3

Technical data

General data and operating conditions

Conformity and approval

CE

2006/95/EC

Low−Voltage Directive

2004/108/EG

EMC Directive

EAC

TP TC 020/2011
(TR CU 020/2011)

Electromagnetic
compatibility of technical
means

Eurasian Conformity
TR CU: Technical Regulation of
Customs Union

TP TC 004/2011
(TR CU 004/2011)

On safety of low voltage
equipment

Eurasian Conformity
TR CU: Technical Regulation of
Customs Union

UL

cULus

Power Conversion Equipment (File No. E132659)

Protection of persons and equipment

Type of protection

EN 60529

IP20

IP41 on the heatsink side for thermally separated mounting
(push−through technique).

NEMA 250

Protection against contact in accordance with type 1

Earth leakage current

IEC/EN 61800−5−1

> 3.5 mA

Observe stipulations and safety
instructions!

Insulation of control
circuits

IEC/EN 61800−5−1

Safe mains isolation through double (reinforced) insulation

Insulation resistance

EN 61800−5−1

< 2000 m site altitude: Overvoltage category III

> 2000 m site altitude: Overvoltage category II

Protective measures

Against short circuit, earth fault (protected against short to
earth on power−up, limited protection against short to earth
during operation), overvoltage, motor stalling, motor
overtemperature (input for PTC thermistor or thermal contact,
I

2

t monitoring)

EMC

Noise emission

IEC/EN 61800−3

Cable−guided, category C1 or C2 when using shielded motor
cables

1)

, dependent on the device variant with integrated

interference suppression or additional RFI/mains filter

0.25 ... 11 kW

E82xVxxxKxC0xx

no additional measures

E82xVxxxKxC2xx

with external filter techniques

15 ... 90 kW

E82EVxxxK4B3xx

no additional measures

E82xVxxxK4B2xx

with external filter techniques

Interference immunity

IEC/EN 61800−3

Category C3

1)

Motor cable lengths depend on the inverter type and the switching frequency