Safety instructions – Lenze E82EV 8200 User Manual

Page 96

Advertising
background image

Safety instructions

Thermal motor monitoring

2

l

96

EDK82EV113 DE/EN/FR 11.0

60

180

240

300

360

t [s]

0.5

0

0

1.0

1.5

2.0

C0054

I

r

120

f = 0 Hz

f = 20 Hz

f > 40 Hz

I x 100 %

I

r

N

C0120 <

I x 100 %

I

r

N

C0120 =

I x 100 %

I

r

N

C0120 >

8200vec523

f

Output frequency

t

Release time

I

N

Rated controller current at switching frequency 8 kHz

I

r

Rated motor current

C0054

Apparent motor current

Example:

C0120

+

I

r

I

N

@ 100 %

C0054 = 1.5 x rated motor current
The controller switches off at output frequencies f > 40 Hz with error OC6 after approx. 60 s.

Setting tips
ƒ To avoid an early response in the case of forced ventilated motors, deactivate the function, if

necessary.

ƒ The current limits C0022 and C0023 only have an indirect effect on the I

2

t calculation.

However, you can prevent the motor from being actuated at the maximum possible
utilisation by the settings of C0022 and C0023.

)

Note!

If the controller is actuated at an increased rated power, the I

2

t monitoring can respond

if C0120 is set to a smaller value than 100 %.