Lenze E82EV 8200 User Manual

Page 131

Advertising
background image

Extensions for automation

Modules

Mounting and dismounting function modules

6

l

131

EDK82EV113 DE/EN/FR 11.0

Mounting

8200vec611

1.

Disconnect the drive controller from mains and wait at least 3 minutes!

2.

Remove the FIF cover

0 from the FIF interface.

3.

Remove protective cap

1 of the function module 2 and plug function module onto the FIF

interface.

4.

Insert the plug connector

3 into the contact strip of the function module until it snaps in.

Additionally fit the retaining clip so that the module cannot be removed together with the terminal
strips

5 during wiring:

5.

Insert the retaining clip

4 into the recess, place it on the function module and latch it.

6.

Wire the function module (see mounting instructions of the function module).

)

Note!

Keep the FIF cover

0 and the protection cover of the function module 1 so that you can

attach them again after you have dismounted the function module.
The controller can only be commissioned if a function module or the FIF cover

0 is

plugged on the FIF interface.

Advertising