Safety instructions

Thermal motor monitoring

2

l

95

EDK82EV113 DE/EN/FR 11.0

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze Selection

C0120 I

2

t switch−off

0

0
= inactive

{1 %}

200 Reference: apparent motor

current (C0054)
Reference to active motor current
(C0056) possible, see C0310

C0311
*

v

Functions for
special
applications 2

1

0

All functions switched off

A combination of functions can be
activated by entering the sum of
the selection values.

1, 2, 4,
8, 16

, System manual

(from software
version 3.9)

1

128

Motor overload (I

2

xt) tart value

Function active:

Function switched−off:

When the device is connected to the
mains, the thermal motor load is
initialised with 50 %.
The function has to be activated for
operation in UL−approved systems.

When the device is connected to
the mains, the thermal motor load
is initialised with 0 % ("cold
engine")

Adjustment
1.

Calculate C0120. This value corresponds to a motor utilisation of 100 %:

C0120 [%]

+

I

r

I

N

@ 100 %

I

r

Rated motor current

I

r

Rated controller current at switching frequency 8 kHz

2.

If you decrease C0120 on the basis of the value calculated, the monitoring already responds at
a motor utilisation < 100 %.

3.

If you increase C0120 on the basis of the value calculated, the monitoring only responds at a
motor utilisation > 100 %.

The controller switches off with error OC6 if the apparent motor current is greater than the rated
motor current for a longer time.