Commissioning – Lenze E82EV 8200 User Manual

Page 142

Advertising
background image

Commissioning

Parameter setting with the XT EMZ9371BC keypad
V/f characteristic control

7

l

142

EDK82EV113 DE/EN/FR 11.0

Comment

Switch−on sequence

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

12.

Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz

13.

Set the V

min

boost (C0016)

Lenze setting: depends on the controller type

The Lenze setting is suitable for all common
applications

14.

Activate the motor temperature monitoring (C0119) if you
have connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off

Possible settings

(

153)

When all settings are complete:

15.

Select setpoint

E.g. via potentiometer at terminals 7, 8, 9

16.

Enable the controller

Terminal X3/28 = HIGH

17.

The drive is now running.

If the drive does not start, additionally press

u