Commissioning – Lenze E82EV 8200 User Manual
Page 142
![background image](/manuals/566001/142/background.png)
Commissioning
Parameter setting with the XT EMZ9371BC keypad
V/f characteristic control
l
142
EDK82EV113 DE/EN/FR 11.0
Comment
Switch−on sequence
8.
Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
9.
Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10.
Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
11.
Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
12.
Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
13.
Set the V
min
boost (C0016)
Lenze setting: depends on the controller type
The Lenze setting is suitable for all common
applications
14.
Activate the motor temperature monitoring (C0119) if you
have connected a PTC or thermal contact to terminal X2.2
Lenze setting: switched off
Possible settings
(
¶ 153)
When all settings are complete:
15.
Select setpoint
E.g. via potentiometer at terminals 7, 8, 9
16.
Enable the controller
Terminal X3/28 = HIGH
17.
The drive is now running.
If the drive does not start, additionally press
u