V/f characteristic control, Commissioning – Lenze E82EV 8200 User Manual

Page 137

Advertising
background image

Commissioning

Parameter setting with E82ZBC keypad

V/f characteristic control

7

l

137

EDK82EV113 DE/EN/FR 11.0

V/f characteristic control

The following instructions apply to controllers equipped with a standard−I/O function module and
a three−phase AC motor which has been selected according to a power−based assignment.

Switch−on sequence

Comment

1.

Connect keypad

2.

Ensure that controller inhibit is active after mains
connection

Terminal X3/28 = LOW

3.

Switch on the mains

4.

The keypad is in "Disp" mode after approx. 2 s and indicates
the output frequency (C0050)

The USEr menu is active

5.

Change to the

f mode to configure the basic settings for

your drive

Blinking on the display: 0050

6.

Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: −0−, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)

Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for
the standard I/O)

7.

Adapt the terminal configuration to the wiring (C0007)
Lenze setting: −0−, i. e.
E1: JOG1/3 fixed setpointselection
E2: JOG2/3
E3: DCB DC brake
E4: CW/CCW rotation

8.

Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz

9.

Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz

10.

Set the acceleration time T

ir

(C0012)

Lenze setting: 5.00 s

11.

Set the deceleration time T

if

(C0013)

Lenze setting: 5.00 s

12.

Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz

13.

Set the V

min

boost (C0016)

Lenze setting: Depending on the controller type

The Lenze setting is suitable for all common
applications

14.

If you want to change the settings, go to the ALL menu

For instance activate JOG frequencies (C0037,
C0038, C0039) or motor temperature
monitoring (C0119)

When all settings are complete:

15.

Select setpoint

E.g. via potentiometer at terminals 7, 8, 9

16.

Enable the controller

Terminal X3/28 = HIGH

17.

The drive is now running.

If the drive does not start, additionally press

u