Wiring terminal strips – Lenze E82EV 8200 User Manual
Page 114
Electrical installation
Wiring
Wiring terminal strips
l
114
EDK82EV113 DE/EN/FR 11.0
Wiring terminal strips
The supplied terminal strips are tested according to the specifications of
ƒ DIN VDE 0627:1986−06 (partially)
ƒ DIN EN 60999:1994−04 (partially)
Checked and tested are, for instance, mechanical, electrical and thermal load, vibration, damage of
conductors, loose conductors, corrosion, ageing.
(
Stop!
Proceed as follows to avoid damage of the terminal strip and the contacts:
ƒ
Mount or remove only when the controller is not connected to the mains!
ƒ
Wire the terminal strips before connecting them!
ƒ
Unused terminal strips must also be plugged in to protect the contacts.
8200vec015
)
Note!
Basically wiring without wire end ferrules is possible.
If safety functions (e.g. "Safe torque off") are used, insulated wire end ferrules or rigid
conductors are required!