Troubleshooting and fault elimination – Lenze E82EV 8200 User Manual

Page 161

Advertising
background image

Troubleshooting and fault elimination

Fault elimination

Fault messages

8

l

161

EDK82EV113 DE/EN/FR 11.0

Remedy

Cause

Fault

PC

1)

Keypad

OC5

a

15

Controller overload
during steady−state
operation

Frequent and too long overload
periods

Check drive dimensioning

OC6

a

16

Motor overload
(I

2

x t overload)

Motor is thermally overloaded by
e.g.

l

impermissible continuous
current

l

Check drive dimensioning

l

frequent or too long
acceleration processes

l

Check setting of C0120

OH

a

50

Heatsink
temperature > +85
°C

Ambient temperature is too high

Allow controller to cool and provide
for better ventilation

OH

e

Heatsink
temperature > +80
°C

Heatsink is very dirty

Clean heatsink

OH

e

Heatsink
temperature > +80
°C

Impermissible high currents or
frequent and too long
acceleration processes

l

Check drive dimensioning

l

Check load, replace
rough−running, defective
bearings, if necessary

OH3

a

53

PTC monitoring
(TRIP)
(display when
C0119 = 1 or 4)

Motor too hot due to
impermissible high currents or
frequent and too long
acceleration processes

Check drive dimensioning

No PTC connected

Connect PTC or switch off monitoring

OH4

a

54

Controller
overtemperature

Controller is too hot inside

l

Reduce controller load

l

Improve cooling

l

Check fan in the controller

OH51

203

PTC monitoring
(display when
C0119 = 2 or 5)

Motor too hot due to
impermissible high currents or
frequent and too long
acceleration processes

Check drive dimensioning

No PTC connected

Connect PTC or switch off monitoring