Troubleshooting and fault elimination

Fault elimination
Fault messages

8

l

158

EDK82EV113 DE/EN/FR 11.0

Remedy

Cause

Malfunction

Motor rotates, setpoints are 0"

With the

j function of the keypad a

setpoint has been selected

Set setpoint to "0" with C0140 = 0

Motor parameter identification
stops with error LP1

Motor is too small in relation to the rated
power of the drive

DC injection brake (DCB) active via terminal

Unacceptable drive response
with vector control

Various

Optimise vector control

Torque dip in the field
weakening range

Various

Contact Lenze

Stalling of the motor when
operating in the field weakening
range

Fault messages

Keypad

PC

1)

Fault

Cause

Remedy

noer

0

No fault

ccr

a

71

System fault

Strong interference injections on
the control cables

Shield control cables

Earth loops in the wiring

ce0

a

61

Communication
error on AIF
(configurable in
C0126)

Faulty transmission of control
commands via AIF

Insert the communication module
firmly into the diagnosis terminal

ce1

a

62

Communication
error on CAN−IN1
with sync control

CAN−IN1 object receives faulty
data, or communication is
interrupted

l

Check plug connection bus
module

ó FIF

l

Check transmitter

l

Increase monitoring time in
C0357/1, if necessary

ce2

a

63

Communication
error on CAN−IN2

CAN−IN2 object receives faulty
data, or communication is
interrupted

l

Check plug connection bus
module

ó FIF

l

Check transmitter

l

Increase monitoring time in
C0357/2, if necessary

ce3

a

64

Communication
error on CAN−IN1
with event or time
control

CAN−IN1 object receives faulty
data, or communication is
interrupted

l

Check plug connection bus
module

ó FIF

l

Check transmitter

l

Increase monitoring time in
C0357/3, if necessary

Advertising