Electrical installation

Mains connection

Connection plan for controllers type E82xVxxxK2C (230/240 V mains)

5

l

117

EDK82EV113 DE/EN/FR 11.0

Mains connection

Connection plan for controllers type E82xVxxxK2C (230/240 V mains)

(

Stop!

ƒ

Only connect the controller to the permitted mains voltage (

^ Technical data). A

higher mains voltage destroys the controller!

ƒ

Some controllers may only be actuated with a mains choke or mains filter. This
requirement can differ with regard to operation at rated power and operation at an
increased rated power.

ƒ

The leakage current to earth (PE) is > 3.5 mA. In accordance with EN 61800−5−1 a
fixed installation is required. The PE conductor has to be designed double.

X1.1

3 PE AC 230/240 V

45Hz -0%...65Hz +0% 100 V -0%...264 V +0%

X1.1

PE L1

L3

+UG -UG

L2

E82EVXXXK C

2

L1
L2
L3

N

PE

0,7...0,8 Nm
6.2...7.1 lb-in

6 mm / 0.24 in

8200vec065

X1.1/+UG, X1.1/−UG

Supply for DC−bus operation