Safety instructions

Safety instructions for the installation according to UL or UR

2

l

99

EDK82EV113 DE/EN/FR 11.0

Safety instructions for the installation according to U

L

or U

R

J

Warnings!

ƒ

Motor Overload Protection

–

For information on the protection level of the internal overload protection for a
motor load, see the corresponding manuals or software helps.

–

If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.

ƒ

Branch Circuit Protection

–

The integral solid state protection does not provide branch circuit protection.

–

Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any additional codes.

ƒ

Please observe the specifications for fuses and screw−tightening torques in these
instructions.

ƒ

E82xV302K2C ... E82xV752K2C (3.0 kW ... 7.5 kW, 240 V devices):

–

Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 240 V maximum, when protected by fuses.

–

Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 240 V maximum. When protected by CC, J, T or R class
fuses.

–

Shall be installed in a Pollution Degree 2 macro−environment.

–

Maximum surrounding air temperature: 0 ... +55 °C

–

> +40 °C: reduce the rated output current by 2.5 %/°C

–

Use 60/75 °C or 75 °C copper wire only.

ƒ

E82xV302K4C ... E82xV113K4C (3.0 kW ... 11 kW, 400/500 V devices):

–

Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers (E82xV302K4C only).

–

Suitable for use on a circuit capable of delivering not more than 50000 rms
symmetrical amperes, 500 V maximum. When protected by CC, J, T or R class
fuses

–

Shall be installed in a Pollution Degree 2 macro−environment.

–

Maximum surrounding air temperature: 0 ... +55 °C

–

> +40 °C: reduce the rated output current by 2.5 %/°C

–

Use 60/75 °C or 75 °C copper wire only.