Commissioning – Lenze E82EV 8200 User Manual

Page 147

Advertising
background image

Commissioning

Important codes for quick commissioning

7

l

147

EDK82EV113 DE/EN/FR 11.0

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0002*

s

uSEr

Parameter set
management

0

0

Ready

PAR1 ... PAR4:

l

Parameter sets of the controller

l

PAR1 ... PAR4 also contain the
parameters for the function
modules standard I/O,
application I/O, AS interface,
system bus (CAN)

FPAR1:

l

Module−specific parameter set of
the fieldbus function modules
INTERBUS, PROFIBUS−DP,
LECOM−B, DeviceNet/CANopen

l

FPAR1 is saved in the function
module

Restoring the
delivery status

1

Lenze setting

ð PAR1

Restore the delivery status in the
parameter set selected

2

Lenze setting

ð PAR2

3

Lenze setting

ð PAR3

4

Lenze setting

ð PAR4

31

Lenze setting

ð FPAR1

Restore the delivery status in the
fieldbus function module

61

Lenze setting

ð PAR1 + FPAR1

Restore the delivery status in the
selected parameter set of the
controller and in the fieldbus function
module

62

Lenze setting

ð PAR2 + FPAR1

63

Lenze setting

ð PAR3 + FPAR1

64

Lenze setting

ð PAR4 + FPAR1

C0002*

s

uSEr

(Cont.)

Transferring
parameter sets
with the keypad

By means of the keypad you can
transfer the parameter sets to other
controllers.
During the transmission the access to
the parameters via other channels is
inhibited!

Keypad

ð controller

Overwrite all available parameter
sets (PAR1 ... PAR4, if required FPAR1)
with the corresponding data of the
keypad

70

with function module application I/O,
INTERBUS, PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen

10

with all other function modules