Fuses and cable cross-sections according to ul, Fuses and cable cross−sections according to ul, Electrical installation – Lenze E82EV 8200 User Manual
Page 121
Electrical installation
Mains connection
Fuses and cable cross−sections according to UL
l
121
EDK82EV113 DE/EN/FR 11.0
Fuses and cable cross−sections according to UL
Supply conditions
Range
Description
Fuses
l
Only in accordance with UL 248
l
System short−circuit current up to 5000 A
rms
: All classes are permissible
l
System short−circuit current up to 50000 A
rms
: Only classes "CC", "J", "T" or "R" permissible
Circuit−breaker
l
Only in accordance with UL 489
l
Manufacturer/type
– ABB: S 200 U Charact. K
– Schneider Electric: Multi9 C60 Charact. C
– Moeller: FAZ−C Charact. C
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
Operation with increased rated power
Operation at an increased rated power is not UL−certified.