Electrical installation

Connection of relay output K

SR

5

l

127

EDK82EV113 DE/EN/FR 11.0

Wiring

}

Danger!

Faulty operation in case of earth faults possible

The correct functioning of the safety function is not ensured if an earth fault occurs.
Possible consequences:

ƒ

A failure of the safety function can lead to death, severe injuries or damage to
material.

Protective measures:

The electrical reference point for the coil of the safety relay K

SR

must be connected to

the PE conductor system (EN 60204−1, paragraph 9.4.3)!

}

Danger!

Danger to life through improper installation

Improper installation of the safety engineering systems may cause an uncontrolled
starting action of the drives.
Possible consequences:

ƒ

Death, severe injuries, or damage to material assets during an uncontrolled starting
action of the drives.

Protective measures:

ƒ

Shielded installation of all control cables connected to the FIF module is essential to
reduce interference injection.

ƒ

Apply the shield to a large surface of the EMC sheet.