Note!

Communication modules can be supplied by an internal or external voltage source. An
external voltage source is only required if communication to a node is to be maintained
in the case of a switch−off or if the node fails.

Mounting

8200vec616

1.

Set the type of voltage supply via the jumper

0.

– Position I: external voltage supply (delivery status; +24 V DC

±10%, max. 100 mA per

module)

– Position II: voltage supply via the internal voltage source

2.

Plug the communication module

1 to the AIF interface on the controller.

3.

If the communication module is provided with a safety screw

2, screw the module together

with the controller.