Troubleshooting and fault elimination

Troubleshooting

Status display via controller LEDs

8

l

155

EDK82EV113 DE/EN/FR 11.0

8

Troubleshooting and fault elimination

Troubleshooting

Detecting breakdowns
A breakdown can be detected quickly via the LEDs at the controller or via the status information at
the keypad.

Analysing errors
Analyse the error using the history buffer. The list of fault messages gives you advice how to remove
the fault. (

158)

Status display via controller LEDs

During operation the operating status of the controller is shown by 2 LEDs.

LED red



LED green

‚

Operating status

Off

On

Controller enabled

On

On

Mains switched on and automatic start inhibited

Off

Blinking slowly

Controller inhibited

Off

Blinking quickly

Motor parameter identification is carried out

Blinking quickly

Off

Undervoltage or overvoltage

Blinking slowly

Off

Fault active, check in C0161

Fault analysis with the history buffer

Retracing faults
Via the history buffer you can retrace faults. Fault messages are saved in the 4 memory locations in
the order of their occurrence. The memory locations can be called via codes.

Structure of the history buffer

Code

Memory location

Entry

Comment

C0161

History buffer location 1

Active fault

If the fault is no longer pending or has been
acknowledged:

l

The contents of memory locations 1 ... 3 are shifted one
memory location "higher".

l

The contents of memory location 4 are no longer
included in the history buffer and cannot be called
anymore.

l

Memory location 1 is deleted (= no active fault).

C0162

History buffer location 2

Last fault

C0163

History buffer location 3

Penultimate fault

C0164

History buffer location 4

Third from last fault