Commissioning

Linear V/f-characteristic control

T

EDK82MV222 DE/EN/FR 9.0

NNP

L

10.

Set the acceleration time T

ir

(C0012)
Lenze setting: 5.00 s

f [ H z ]

f 2

C 0 0 1 1

f 1

0

t i r

t i f

T i r

T i f

t

T

ir

= t

ir

C0011

f2 − f1

t

ir

= acceleration time

wanted

11.

Set the deceleration time T

if

(C0013)
Lenze setting: 5.00 s

T

if

= t

if

C0011

f2 − f1

t

if

= deceleration time

wanted

12.

Set the V/f-rated frequency

(C0015)
Lenze setting: 50.00 Hz

NMMB

M

M

`MMNR

s

ãáå

s

змн

С

13.

Set the V

min

boost (C0016)

Lenze setting: Depends on the

controller type

The Lenze setting is

suitable for all common

applications

14.

If you want to change other
settings, please go to the

ALL

menu

Activate e.g. JOG frequencies

(C0037, C0038, C0039) or motor

temperature monitoring (C0119)

15.

Go to the

ALL

menu

A Check the fan monitoring

setting under code C0608:
– for 8200 motec 0.25...0.37

kW and 0.55...2.2 kW:

C0608 = 0! (default setting)

– for 8200 motec 3...7.5 kW:

C0608 =1 (recommended)

or C0608 = 2!

Stop!

Function must be

activated during

commissioning!

Otherwise, the

controller may be

destroyed through

overheating!

– for all other controllers:

C0608 = 0 ! (default

setting)

B Select additional functions via

codes, if necessary.

When all settings are complete:
16.

Select the setpoint

E.g. via potentiometer at

terminals 7, 8, 9

17.

Enable the controller

20

28

X3

misc002

Terminal X3/28 = HIGH

18.

The drive should now be running.

If the drive does not

start, press  in

addition