Commissioning, Vector control – Lenze E82MV 8200 motec 0.55kW-2.2kW User Manual

Page 117

Advertising
background image

Commissioning

Vector control

T

EDK82MV222 DE/EN/FR 9.0

NNT

L

16.

If necessary, change other

parameters

Activate e.g. JOG frequencies

(C0037, C0038, C0039) or motor

temperature monitoring (C0119)

17.

Go to the

ALL

menu

A Check the fan monitoring

setting under code C0608:
– for 8200 motec 0.25...0.37

kW and 0.55...2.2 kW:

C0608 = 0! (default setting)

– for 8200 motec 3...7.5 kW:

C0608 =1 (recommended)

or C0608 = 2!

Stop!

Function must be

activated during

commissioning!

Otherwise, the

controller may be

destroyed through

overheating!

– for all other controllers:

C0608 = 0 ! (default

setting)

B Select additional functions via

codes, if necessary.

When all settings are complete:
18.

Select the setpoint

E.g. via potentiometer at

terminals 7, 8, 9

19.

Enable the controller

20

28

X3

misc002

Terminal X3/28 = HIGH

20.

The drive should now be running.

If the drive does not

start, press  in

addition